FLAME PROOF MOTORS EX (d)

Table : 1

Zone

Classification of area as per IS : 5572 ( Part 1 ) Selection of electrical equipment based on IS : 5571
Zone
' 0 '
An area in which hazardous atmosphere is continuously present. Generally use of electrical equipment is to be avoided but when this is not practicable intrinsically safe or pressurized electrical equipment may be permitted to be used in such areas.
Zone
' 1 '
Hazardous atmosphere is likely to be present at any time under normal operating conditions. For this area, electrical equipment used, must be in a flame proof enclosure type (Ex) d as specified by IS 2148
Zone
' 2 '
In this area hazardous atmosphere is likely to be present only under abnormal operating conditions and for a short period. Rotating electrical machines having sliding contacts, centrifugal switches etc.  which is normal operation can cause arcing must be enclosed in flame proof enclosures.  Apparatus with type of  protection  (Ex)e in accordance with IS-6381 may be used without any special enclosure.
Apparatus having type of protection (Ex)n in accordance with IS:8289 are also permitted for use.  Three phase induction

Table : 2

Temp. Class as per IS : 6381 & IEC 79-7

Ignition
Temperature - C

    Above Upto and including
T1 450 -
T2 300 450
T3 200 300
T4 135 200
T5 100 135
T6 85 100

Classification of Hazardous Gases :

Hazardous gases have been classified in IS : 2148, VDE 0171 & 5572 (Pt 1) and are associated only with flame proof enclosures.  These gases are listed in Table 3.

Note : Flame Proof motors are offered suitable for Gas Groups I, IIA & IIB only.  For gases not mentioned, please refer the relevant Indian Standards.

Table : 3

Gas Group

Gas or Vapour

Temp. Class
I Methane ( Firedamp) T1
IIA Ammonia T1
  Industrial methane* T1
  Carbon monoxide T1
  Propane T1
  Butane T2
  Benzene T1
   Cyclohexane T2
  Acetone T1
  Ethyl acetate T1
  Methanol T1
  Ethanol T1
  n-Butanol T1
IIB  1,3-Butadiene T1
  Ethylene T1
  Diethyl ether T4
  Ethylene oxide T1
  Coke-oven gas T1
IIC Hydrogen T1

* Industrial methane includes methane mixed with not more than 10% by volume of hydrogen.

Approval Certificates :

Electric equipments used in Zone 1 must by tested by CMRI- Dhanbad.

Approval certificates are issued by the relevant authorities given below on the basis of the test report issued by CMRI.  All BBL motors have been approved by the relevant authorities. 
i.e. DGMS - Dhanbad 
     CCE-  Nagpur
     DGFASLI - Mumbai

All flame proof motors have Licence Mark IS 2148.
A DGMS identification mark must be fitted on the motor for Gas Group I or Oil Mines application.

       Special Features :-

Voltage Single or dual voltage from 110V to 660V
Frequency Ranging from 25Hz to 60 Hz
Attitude Higher than 1000M from mean sea level.
Output Dual output /Dual speed with dahlander connection or separate winding.
Shaft Longer shaft lesser diameter.
Construction B6, B7, B8, V1, V3, V5, V6, B3/B5
Anti Condensation Heater For all frame sizes.
Cable entry* Plug & socket arrangement for all frame sizes.
Re-greasing arrangement* For all frame sizes above and including MJ 160
Flameproof motor for crane duty application can also be offered against enquiries.
* Only for FLP motors