INCREASED SAFETY MOTORS Ex (e)


The motors of increased safety design (type ME) have been developed from the standard TEFC, 3-Phase cage induction motors (type MA) for operation in hazardous locations classified as zone-2 areas as per IS:5572 and VDE 0165

Limited Temperatures :  Limited temperatures for insulation and all parts as specified in IS : 6381 are given in Table 4.
Temp. Class T1 T2 T3 T4 T5 T6
Lower limit of Ignition Temp (0C) 450 300 200 135 100 85
Limited Temp. of rotor at end of the time tE (0C) 450 300 200 135 100 85
Limited temp. of stator  : Class B 185 185 185 135 100 85
Winding at the end of time : Class F
end of time tE (0C)
210 210 200 135 100 85
Limited temp. of stator winding in 
Continuous operation (0C) Class B
                                      Class F

110
130

110
130

110
130

110
110

100
100

85
85

Manufacturing Range :-

ME motors are designed for temperature class (Ignition Temperature Group) T3, Motor types, frame sizes, outputs and other performance details are furnished in the performance / selection tables.

Time 'tE' of Increased Safety Motors :-

Time 'tE' is the locked rotor withstand time.  It is the time taken for heating up any part of the motor from the steady state temperature up to the limiting temperature under the locked rotor condition.  This time is determined separately for stator and rotor and the minimum one is taken as the tE.

The current dependent protective devices must be so selected that the stalled motor will be disconnected positively within the time tE, temperature class and starting current are indicated on the name plate of ME motors.

The starting time normally permitted for these motors is upto 1.5 times the time tE i.e. upto 1.5 x tE.  If starting time is approximately of the order of tE, motor protection becomes difficult, since over current protection may operate spuriously in a repeated start.  Hence, for heavy and frequent starting, an enquiry should be made starting :
a) Duty Cycle
b) GD2 value of driven equipment referred to motor, and
c) Speed-Torque characteristic of the driven equipment.

Increased Safety motors have time tE of minimum 5 seconds.

Voltage Single or dual voltage from 110V to 660V
Frequency Ranging from 25Hz to 60 Hz
Attitude Higher than 1000M from mean sea level.
Output Dual output /Dual speed with dahlander connection or separate winding.
Shaft Longer shaft lesser diameter.
Construction B6, B7, B8, V1, V3, V5, V6, B3/B5
Anti Condensation Heater For all frame sizes.
Cable entry* Plug & socket arrangement for all frame sizes.
Re-greasing arrangement* For all frame sizes above and including MJ 160
Flameproof motor for crane duty application can also be offered against enquiries.